Thermidistat™ Control
Installation, Start-Up, and Operating Instructions
NOTE: Read the entire instruction manual before starting the
installation.
This symbol indicates a change since the last issue.
INDEX
Page
SAFETY CONSIDERATIONS.....................................................1
INTRODUCTION..........................................................................1
INSTALLATION CONSIDERATIONS.......................................1
INSTALLATION........................................................................2-8
Thermidistat Control Location .................................................2
Set DIP Switches ......................................................................2
Install Thermidistat Control ..................................................2-3
Set Thermidistat Control Configuration ...............................3-7
System Start-Up and Checkout.............................................7-8
Final Settings ............................................................................8
HUMIDITY CONTROL FEATURES.....................................8-11
Humidification ..........................................................................8
Dehumidification .................................................................9-10
Vacation.............................................................................10-11
OPERATIONAL INFORMATION.............................................11
THERMIDISTAT CONTROL TROUBLESHOOTING ............11
THERMIDISTAT CONTROL CONFIGURATION RECORD.12
WIRING DIAGRAM..............See Thermidistat Wiring Diagrams
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Follow all
local electrical codes during installation. All wiring must conform
to local and national electrical codes. Improper wiring or installa-
tion may damage Thermidistat Control.
Recognize safety information. This is the safety-alert symbol
.
When you see this symbol on the equipment and in the instruction
manual, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies a hazard which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.
INTRODUCTION
Carrier’s 7-day programmable/non-programmable Thermidistat
Control is a wall-mounted, low-voltage control which combines
temperature and humidity control in a single attractive unit. An
extension of Carrier’s proven line of thermostats, it provides
separate set points for heating and cooling, and now adds humidi-
fication and dehumidification. Different heating and cooling set
points and times are programmable for 4 periods per day and 7
days per week. The Thermidistat Control can also be field-
configured as a non-programmable thermostat. When operating in
the non-programmable configuration it will still have both tem-
perature and humidity control. Humidify and dehumidify outputs
provide direct control of humidity. Batteries are not used. During
power loss an internal memory stores programs and settings for
unlimited time, and the clock continues to run for at least 8 hr.
INSTALLATION CONSIDERATIONS
POWER
Note that this control does not require batteries and is not "power
stealing." It does require 24vac (R and C terminals) of the
low-voltage transformer to be connected to it for proper operation.
It will not operate without these 2 connections.
MODELS
There is a single programmable/non-programmable model for all
applications. It can be configured for AC or HP, 1- or 2-speed
compressor, and for dual fuel installations, allowing it to be used
in place of all Carrier thermostats.
HUMIDIFY EQUIPMENT AND CONNECTIONS
The humidify output connects directly to 24vac operated humidi-
fiers. No other connection or interlock is required. Any of several
installer-selectable operating modes are available.
DO NOT connect Furnace HUM terminal directly to
Thermidistat HUM terminal. This will bypass furnace safety
controls. See Low Voltage Wiring Daigrams and notes for
proper connection.
DEHUMIDIFY EQUIPMENT AND CONNECTIONS
The dehumidify output connects to the dehumidify input on
variable-speed furnaces and fan coils. Additional dehumidification
is done by controlling the compressor. A variety of operating
modes are available.
OUTDOOR TEMPERATURE SENSOR
Optimum performance is obtained when an outdoor temperature
sensor is used with the Thermidistat Control. Plan installation so
that 2 wires can be run from Thermidistat Control to an outdoor
location, preferably on the north side of the house or refer to
Installation Instructions included with the outdoor temperature
sensor for simplified connection. Sensor can be mounted to
outdoor unit and existing control wires may be used for its
connection. Details are provided in sensor instructions.
Fig. 1—Thermidistat Control
HEIGHT (IN.) WIDTH (IN.) DEPTH (IN.)
4-3/8 7-3/8 1-3/8
A98426
Visit www.carrier.com
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab misc. misc.
PC 101 Catalog No. 03TS-TA17 Printed in U.S.A. Form TSTAT-23SI Pg 1 8-99 Replaces: TSTAT-19SI
Vista de página 0
1 2 3 4 5 6 ... 11 12

Resumo do Conteúdo

Página 1 - Thermidistat™ Control

Thermidistat™ ControlInstallation, Start-Up, and Operating InstructionsNOTE: Read the entire instruction manual before starting theinstallation.This s

Página 2

humidity removal is desired, this should be done, if possible. Fancoils have the capability of removing this off delay, furnaces donot. On FK or FV Fa

Página 3

Vacation DehumidificationNormal Dehumidify, Cool to Dehumidify, and Dehumidify OFF,are all available in vacation mode, and selection of 1 of these can

Página 4

THERMIDISTAT CONTROL CONFIGURATION RECORDDateOwner/OperatorA) Hardware Configuration Switch A ____ AC/HP Select. (OFF = AC) Switch B ____ 1 or 2-Sp

Página 5 - Table 1—W1 / W2 Outputs

INSTALLATIONStep 1—Thermidistat Control LocationThermidistat Control should be mounted:• Approximately 5 ft (1.5m) from floor.• Close to or in a frequ

Página 6

3. A2—for 2-speed air conditioner4. H2—for 2-speed heat pump5. dF—for 1-speed dual fuel6. d2—for 2-speed dual fuel7. HS—for 1-speed heat pump with Int

Página 7

3. Use up and down buttons to move between F and C on largedisplay.4. Press SET TIME/TEMP button again to flash upper smalldisplay for selection of an

Página 8 - Table 2—Equipment Outputs

Option 10—Dual Fuel EquipmentAll dual fuel installations must be equipped with a highpressure switch to turn off compressor under a high indoorcoil pr

Página 9

will be supplied, resulting in additional outputs being turned on. Ifroom overheats, specified outputs will not turn off, guaranteeing asufficiently w

Página 10

3. Use up and down buttons to move between OF and ON onlarge display. Factory default is OF.4. Press SET TIME/TEMP button again to flash upper smalldi

Página 11

TO TEST COOLING AND DEHUMIDIFICATION:Press MODE button until COOL icon turns on. Cooling beginswithin 10 sec and remains on for 4 minutes. If system i

Página 12 - WAKE DAY EVE SLEEP

4. Auto and Fan HumidifyThe 2 choices of AUTO and FAN can be selected together.This provides both functions simultaneously.5. Humidify OffThe humidify