6-10 August 2003 Access Navigator - Release 1.8
Electrical Installation
Prepare DSX-1 Cables
Figure 6-3. DSX-1 Cable with Two Connectors (PN 005-0025)
2. If DSX-1 cables with flying wires are needed for wire-wrap or splice connections, cut off one
connector and strip back the insulation (see Figure 6-4).
Do not cut off connector with shield drain wire unless cable has shield drain wires at both ends.
(Shield drain wire must be attached to Access Navigator.)
Cut off one connector to produce cable of desired length.
Strip back insulation to produce flying wires of desired length. (Leave some of inner bundle
wrap exposed to identify wire bundle color codes.)
NOTE: ABAM shielded cable is recommended for extending DSX-1 connections.
Figure 6-4. DSX-1 Cable with Flying Wires
Shield drain wire
with ground lug
64-Pin Connector
DSX-1 cable is 10 ft (3m) long
CAC
Part Number
Do not ground second
shield drain wire. Use
only to extend shield
to extension cables.
Shield drain wire
with ground lug
64-Pin Connector
DSX-1 cable is 10 ft (3m) long
Group 1, Blue Wrap
DS1 #1 to #12
Group 2, Blue Wrap
DS1 #13 to #25
Group 3, Orange Wrap
DS1 #26 to #32
Color coded wires
CAC
Part Number
Color
wrap